When choosing the FM-200 gas suppression system, you can refer to the following regulations:
Regulations on the number of equipment when installing FM-200 gas suppression systems in the protected area
1.When an FM-200 gas suppression system is used for two or more protected areas, it should not cover more than 8 protected areas.
2.There should be no more than 10 devices of FM-200 gas suppression system installed in a protected area.
3.When there is more than one gas suppression system device in one protected area, they can be started together if necessary, but the time difference between the actions of the devices should not be longer than 2 seconds.
Regulations for the area and volume of the places FM-200 gas suppression system is installed
1.The protected area should be divided into single enclosed spaces. When the ceiling and under-floor in the same section need to be protected together, they can be combined into one protected area.
2.When using a networking gas suppression system, its protecting area should not be larger than 800m², and the volume should not be larger than 3600m³.
3.When using a pre-engineered gas suppression system, its protecting area should not be larger than 500m², and the volume should not be larger than 1600m³.